Toroidal Ring Type Current Transformers

Description

A range of ring type current transformers suitable for primary currents from 1A-5000A with 1A or 5A secondaries. This standard range of measuring and protective current transformers is available as resin coated or tape wrapped.

Application
Suitable for measuring or protective applications with accuracies of class 0.2, 0.5, 1, 3, 5P10, 10P10 etc.

  • Primary currents from 1A - 5000A.
  • Measuring or Protective types.
  • Base or busbar mounting.
  • Choice of sizes to customers specification
  • Conforms to IEC 44-1, IEC 185, and BS7626.
  • Rated system voltage 0.72 / 3kV.
  • Ambient temperature range -30ºC to 85ºC.
  • Frequency Range 5-60Hz.
  • Insulation Level, 3kV (50Hz for 1 minute.

Test Certificates
Our production facilities allow automated printing of test cetificates for individual current transformers, if requested.

Terminal Covers
Ring type current transformers can be provided with sealable terminal covers. Please specify on your order if  required.

Burden
When choosing the VA of a current transformer, the burden of the instrument should be taken into account. For example, moving iron panel meters require a VA of less than 2.5 . Where possible the instrument is remote from the CT, the VA imposed by the length of the connection wires should be taken into consideration. The graph opposite outlines the effect of connection wire length on VA.

ct7

Multiple Primary Turns

The ratio of a current transformer can be reduced by passing more than one conductor turn through the centre of the CT. The ratio will therefore be the CT primary divided by the number of turns. For example, a 400/5A CT with 2 primary turns passed through the centre, will provide an actual ratio of 200/5A