The RVS1000 Series compact, low-profile DC/AC inverter utilizes established design techniques to deliver 1000VA sine wave voltage. Suitable for a wide range of applications, the RVS1000 features full electronic protection, high efficiency and low output noise.

Internal modules are encapsulated within a thermally conductive MIL-spec silicon rubber compound to ensure resistance against shock, vibration, moisture, humidity, salt, fog, dust, and insects. The unit is conduction cooled. Extended operating temperature ranges are available.

The RVS1000 is housed in a 19”x14”x 3” chassis-mount enclosure. The demonstrated MTBF of the unit exceeds 250,000 hours.

Features

  • Input is filtered to EN 55022 Class A (minimum)
  • Low Profile, Compact Size
  • Sinusoidal wave shape
  • 1000VA of output power
  • Full electronic protection
  • Field-proven design topology
  • Applications

  • Marine / Automotive / RV
  • Electric Utilities and Substations
  • Telecom Power Plants
  • Manufacturing Locations
  • Steel Mills
  • Military Applications (COTS)
  • Industrial Controls
  • OEM Applications
  • Solar / Alternative Power Systems
  • Fuel Cells
  • Electrical [Input/Output]/ Mechanical Specification
    Input Voltage 24V, 36V, 48V, 125V, 250VDC +20% / -15% are standard
    Consult factory for other inputs
    Input Protection Thermal fuse / Inrush current limiting / Reverse polarity protection
    Isolation Input to chassis: 1500VDC / Input to output: 3000VDC/ Output to chassis: 2250VDC
    Output Voltage 115VAC @ 8.7A or 230V @ 4.34A continuous at 50, 60 or 400Hz with grounded neutral
    Isolated floating output optional
    (Consult factory for other output requirements)
    Wave Form Sinusoidal
    Total Harmonic Distortion Less than 5% at full load
    Efficiency Min. 78% at full load
    Line Regulation Better than 0.5%
    Load Regulation Better than ± 2% from no load to full load
    Output Protection Current limiting with short circuit protection, thermal shutdown with
    automatic recovery in case of continuous overload or insufficient airflow
    EMI EN 55022 Class A as a minimum
    Load Crest Factor Maximum 3.0 at 90% load
    Operating Temperature Range 0 °C to +50°C (Wider temperature range available)
    Humidity 5 - 95% non-condensing
    Temperature Drift 0.05% per °C over operating temperature range
    Packaging Fully encapsulated and potted internal modules
    Dimensions 19” x 14” x 2.7” enclosed case
    Connections Input/output: compression-type terminal block
    (Phoenix SMKDS 5/3-9,6)
    Weight 15 lb (7 kg)
    Safety Designed to meet C22.2 No. 107.1 - 01, UL 458 , EN60950 and EN50155
    Options Output Fail Alarm (Form C) Remote Inhibit: By closing external contacts on the inhibit terminals
    Warranty: Twenty Four months subject to application within good engineering practice
    Enhancements to these general specifications can be accommodated upon request
    Designed to meet common approval requirements. Specifications Subject to Change Without Notice
    Designed and Manufactured in Canada